Central heating energy efficiency class
A
A
A
A
A
Energy efficiency class, DHW heating
-
-
-
A
A
Rated heating output at 80/60°C (kW)
13.5
18.9/22.2
23.8/27.1
18.9/22.2
23.8/27.1
Rated heating output at 50/30°C (kW)
15.2
20.4
25.8
20.4
25.8
Rated heat input (kW)
14
19.6/23.0
24.6/28.0
19.6/23.0
24.6/28.0
Lowest heating output (modulating)
At 80/60°C (kW)
1.8/4.6
3.8/6.8
4.8/6.8
3.8/6.8
4.8/6.8
At 50/30°C (kW)
2.1/5.4
4.4/7.4
5.6/7.4
4.4/7.4
5.6/7.4
Lowest heat input (modulating) (kW)
1.9/4.9
3.9/6.9
4.9/6.9
3.9/6.9
4.9/6.9
Heating flow connection (Thread)
¾“ (DN 20)
¾“ (DN 20)
¾“ (DN 20)
¾“ (DN 20)
¾“ (DN 20)
Heating return connection (Thread)
¾“ (DN 20)
¾“ (DN 20)
¾“ (DN 20)
¾“ (DN 20)
¾“ (DN 20)
Cold water connection / DHW circulation (Thread)
¾“
¾“
¾“
¾“
¾“
Cold water connection (Thread)
¾“
¾“
¾“
¾“
¾“
Gas connection (R)
½“
½“
½“
½“
½“
Balanced flue connection (mm)
60/100
60/100
60/100
60/100
60/100
Depth (mm)
378
378
378
378
378
Width (mm)
440
440
440
440
440
Height (mm)
790
790
790
790
790
Total weight (kg)
33
33
33
33
33
Balanced flue (Type)
B23P, B33P, C13(x), C33(x), C43(x), C53(x), C63(x), C83(x), C93(x)
B23P, B33P, C13(x), C33(x), C43(x), C53(x), C63(x), C83(x), C93(x)
B23P, B33P, C13(x), C33(x), C43(x), C53(x), C63(x), C83(x), C93(x)
B23P, B33P, C13(x), C33(x), C43(x), C53(x), C63(x), C83(x), C93(x)
B23P, B33P, C13(x), C33(x), C43(x), C53(x), C63(x), C83(x), C93(x)
Gas category
II2N3P
II2N3P
II2N3P
II2N3P
II2N3P
Natural gas E/H (net cv = 9.5 kWh/m³ = 34.2 MJ/m³) (m³/h)
1.44
2.06/2.42
2.52/2.95
2.06/2.42
2.52/2.95
Natural gas LL (net cv = 8.6 kWh/m³ = 31.0 MJ/m³) (m³/h)
1.59
2.28/2.67
2.79/3.25
2.28/2.67
2.79/3.25
LPG P (net cv = 12.8 kWh/m³ = 46.1 MJ/m³) (kg/h)
1.07
1.53/1.80
1.87/2.19
1.53/1.80
1.87/2.19
Natural gas (permissible min./max.) (mbar)
20(17-25)
20(17-25)
20(17-25)
20(17-25)
20(17-25)
LPG (permissible min./max.) (mbar)
50(42.5-57.5)
50(42.5-57.5)
50(42.5-57.5)
50(42.5-57.5)
50(42.5-57.5)
Standard seasonal efficiency [to DIN] at 40/30°C (net cv/gross cv) (%)
110/99
110/99
110/99
110/99
110/99
Standard seasonal efficiency at 75/60°C (net cv/gross cv) (%)
107/96
107/96
107/96
107/96
107/96
At rated load at 80/60°C (net cv/gross cv) (%)
98/88
98/88
98/88
98/88
98/88
At 30% partial load and TR = 30°C (net cv/gross cv) (%)
108/97
108/97
108/97
108/97
108/97
Flow temperature, factory setting (°C)
75
75
75
75
75
Flow temperature up to approx. (°C)
90
90
90
90
90
Max. total pressure (bar)
3
3
3
3
3
High-efficiency pump (EEI < 0.23)
600 l/h pump rate (14 kW at Δt = 20 K) (mbar)
550
550
550
550
550
860 l/h pump rate (20 kW at Δt = 20 K) (mbar)
-
430
430
430
430
1030 l/h pump rate (24 kW at Δt = 20 K) (mbar)
-
-
280
-
280
DHW flow rate (l/min)
-
-
-
2.0-6.5
2.0-8.0
Minimum flow pressure to EN 625 (bar)
-
-
-
0.4
0.65
Spec. water throughput “D” at ΔT = 30 K (l/min)
-
-
-
10.3
13
Max. permissible total pressure, DHW (bar)
-
-
-
10
10
DHW temperature range (adjustable) (°C)
-
-
-
45-65
45-65
DHW capacity of heating water heat exchanger (litres)
1.3
1.3
1.3
1.3
1.3
Expansion vessel, total capacity (Litre)
10
10
10
10
10
Expansion vessel, pre-charge pressure (bar)
0.75-0.95
0.75-0.95
0.75-0.95
0.75-0.95
0.75-0.95
Flue gas temperature 80/60-50/30 at Qmax (°C)
62-45
70-50
76-50
70-50
76-50
Flue gas temperature 80/60-50/30 at Qmin (°C)
30-25
30-25
33-27
30-25
33-27
Available gas fan draught
at Qmax (Pa)
125
135
180
135
180
Flue gas category
G52
G52
G52
G52
G52
Amount of condensate at 50/30°C (l/h)
approx. 1.4
approx. 2.0
approx. 2.4
approx. 2.0
approx. 2.4
Condensate pH value
approx. 4.0
approx. 4.0
approx. 4.0
approx. 4.0
approx. 4.0
Power consumption on standby (W)
3
3
3
3
3
Maximum power consumption (W)
17-45/59
17-51/63
17-62/88
17-51/63
17-62/88
IP rating (IP)
IP X4D
IP X4D
IP X4D
IP X4D
IP X4D
Electrical connection/fuse protection
230 V / 50 Hz / 16 A/B
230 V / 50 Hz / 16 A/B
230 V / 50 Hz / 16 A/B
230 V / 50 Hz / 16 A/B
230 V / 50 Hz / 16 A/B