Central heating energy efficiency class
A
A
A
Energy efficiency class, DHW heating
A
A
A
Rated heating output at 80/60°C (kW)
13.5
18.9/22.2
23.8/27.1
Rated heating output at 50/30°C (kW)
15.2
20.4
25.8
Rated heat input (kW)
14
19.6/23.0
24.6/28.0
Lowest heating output (modulating)
At 80/60°C (kW)
1.8/4.6
3.8/6.8
4.8/6.8
At 50/30°C (kW)
2.1/5.4
4.4/7.4
5.6/7.4
Lowest heat input (modulating) (kW)
1.9/4.9
3.9/6.9
4.9/6.9
Heating flow connection (Thread)
¾“ (DN 20)
¾“ (DN 20)
¾“ (DN 20)
Heating return connection (Thread)
¾“ (DN 20)
¾“ (DN 20)
¾“ (DN 20)
Cold water connection / DHW circulation (Thread)
½“
½“
½“
Cold water connection (Thread)
¾“
¾“
¾“
Balanced flue connection (mm)
60/100
60/100
60/100
Total weight (kg)
54(35+19)
54(35+19)
54(35+19)
Balanced flue (Type)
B23P, B33P, C13(x), C33(x), C43(x), C53(x)
B23P, B33P, C13(x), C33(x), C43(x), C53(x)
B23P, B33P, C13(x), C33(x), C43(x), C53(x)
Gas category
II2N3P
II2N3P
II2N3P
Natural gas E/H (net cv = 9.5 kWh/m³ = 34.2 MJ/m³) (m³/h)
1.44
2.06/2.42
2.52/2.95
Natural gas LL (net cv = 8.6 kWh/m³ = 31.0 MJ/m³) (m³/h)
1.59
2.28/2.67
2.79/3.25
LPG P (net cv = 12.8 kWh/m³ = 46.1 MJ/m³) (kg/h)
1.07
1.53/1.80
1.87/2.19
Natural gas (permissible min./max.) (mbar)
20(17-25)
20(17-25)
20(17-25)
LPG (permissible min./max.) (mbar)
50(42.5-57.5)
50(42.5-57.5)
50(42.5-57.5)
Standard seasonal efficiency [to DIN] at 40/30°C (net cv/gross cv) (%)
110/99
110/99
110/99
Standard seasonal efficiency at 75/60°C (net cv/gross cv) (%)
107/96
107/96
107/96
At rated load at 80/60°C (net cv/gross cv) (%)
98/88
98/88
98/88
At 30% partial load and TR = 30°C (net cv/gross cv) (%)
108/97
108/97
108/97
Flow temperature, factory setting (°C)
75
75
75
Flow temperature up to approx. (°C)
90
90
90
Max. total pressure (bar)
3
3
3
High-efficiency pump (EEI < 0.23)
600 l/h pump rate (14 kW at Δt = 20 K) (mbar)
550
550
550
860 l/h pump rate (20 kW at Δt = 20 K) (mbar)
-
430
430
1030 l/h pump rate (24 kW at Δt = 20 K) (mbar)
-
-
280
Max. permissible total pressure, DHW (bar)
10
10
10
DHW temperature range (adjustable) (°C)
-
45-65
45-65
DHW capacity of heating water heat exchanger (litres)
1.3
1.3
1.3
Nominal capacity of stratification cylinder / equivalent nominal capacity (litres)
44/100
44/120
44/140
Spec. water throughput “D” at ΔT = 30 K (l/min)
14.3
18
20
Continuous DHW output (l/h (kW))
366 (14.6)
560 (23.1)
684 (27.8)
Performance factor to DIN 4708 (NL)
0.8
1.1
1.5
DHW output (l/10 min)
115
150
171
Standby heat loss to EN 12897 (kWh/24 h)
0.8
0.8
0.8
Corrosion protection, DHW heat exchanger / cylinder
Stainless steel
Stainless steel
Stainless steel
Expansion vessel, total capacity (Litre)
10
10
10
Expansion vessel, pre-charge pressure (bar)
0.75-0.95
0.75-0.95
0.75-0.95
Flue gas temperature 80/60-50/30 at Qmax (°C)
62-45
70-50
76-50
Flue gas temperature 80/60-50/30 at Qmin (°C)
30-25
30-25
33-27
at Qmax (g/s)
6.2
8.8/10.7
10.9/13.0
Available gas fan draught
Flue gas category
G52
G52
G52
Amount of condensate at 50/30°C (l/h)
approx. 1.4
approx. 2.0
approx. 2.4
Condensate pH value
approx. 4.0
approx. 4.0
approx. 4.0
Power consumption on standby (W)
3
3
3
Maximum power consumption (W)
17-45/93
17-51/110
17-62/135
IP rating (IP)
IP X4D
IP X4D
IP X4D
Electrical connection/fuse protection
230 V / 50 Hz / 16 A/B
230 V / 50 Hz / 16 A/B
230 V / 50 Hz / 16 A/B