Specifications 

CEW-1
Model type
CEW-1-200
CEW-2-200
General data
Cylinder volume
litres
180
Standby heat loss
kWh/24 h
1.5
1.21
Continuous cylinder output, flow temp. 80/60°C - DHW 10/45°C
kW - l/h
20/490
Output factor (heating)
NL60
2.9
3
Output factor (heating)
NL50
1.4
1.6
Heat-up time 10 kW - 10-50°C
Min.
59
60
Draw-off rate, DHW at 40°C (Tcyl = 55°C, 15 l/min)
litres
191
191
Primary heating water
bar/°C
´3/95
Secondary DHW
bar/°C
`10/95
Internal flange diameter
mm
DN 110
Cold water connection
R1“
Heating return
1½“ male thread
R1“
Circulation
¾“ male thread
R1“
Heating flow
1½“ male thread
R1“
DHW connection
R1“
Protective anode
1¼“ female thread
Electric booster heater
1½“ female thread
-
Sensor well, cylinder sensor (mounted)
1½“ female thread
Indirect coil surface area, heating
2.3
2.3
Indirect coil capacity, heating
litres
17
17
Dimensions
Cold water connection
A mm
90
-
Heating return
B mm
222
-
Heating cylinder sensor
C mm
590
472
Circulation
D mm
697
-
Heating flow
E mm
797
-
DHW connection
F mm
1194
-
Total height
I mm
1290
1290
Diameter including insulation
J mm
600
-
Casing width / depth
mm
600 x 650
650 x 690
Service flange
L mm
324
322
Height when tilted
mm
1395
1410
Weights
Weight
kg
147
145

Specifications 

CEW-1
General data
Cylinder volume (litres)
180
Standby heat loss (kWh/24 h)
1.5
1.21
Continuous cylinder output, flow temp. 80/60°C - DHW 10/45°C (kW - l/h)
20/490
Output factor (heating) (NL60)
2.9
3
Output factor (heating) (NL50)
1.4
1.6
Heat-up time 10 kW - 10-50°C (Min.)
59
60
Draw-off rate, DHW at 40°C (Tcyl = 55°C, 15 l/min) (litres)
191
191
Primary heating water (bar/°C)
´3/95
Secondary DHW (bar/°C)
`10/95
Internal flange diameter (mm)
DN 110
Cold water connection
R1“
Heating return
1½“ male thread
R1“
Circulation
¾“ male thread
R1“
Heating flow
1½“ male thread
R1“
DHW connection
R1“
Protective anode
1¼“ female thread
Electric booster heater
1½“ female thread
-
Sensor well, cylinder sensor (mounted)
1½“ female thread
Indirect coil surface area, heating (m²)
2.3
2.3
Indirect coil capacity, heating (litres)
17
17
Dimensions
Cold water connection (A mm)
90
-
Heating return (B mm)
222
-
Heating cylinder sensor (C mm)
590
472
Circulation (D mm)
697
-
Heating flow (E mm)
797
-
DHW connection (F mm)
1194
-
Total height (I mm)
1290
1290
Diameter including insulation (J mm)
600
-
Casing width / depth (mm)
600 x 650
650 x 690
Service flange (L mm)
324
322
Height when tilted (mm)
1395
1410
Weights
Weight (kg)
147